TC-Link™ Wireless Thermocouple System

Uygulamalar:  

İnşaat malzemesi takibi( beton sertleşmesi )
İleri seviyeli üretim( plastik işleme , kompozit malzeme takibi )
Montaj hattı kontrolü
Gıda sistemleri( dondurucu izleme )
  Kablosuz sensör ağı tabanlı bakım

Özellikler:

Thermocouple (TC) inputs supported

J,K,R,S,T,E (software selectable), single input channel

Standard thermocouple measurement range

J 0 to 760 degrees C.
K 0 to 1370 degrees C.
R 0 to 1000 degrees C.
S 0 to 1750 degrees C.
T -160 to 400 degrees C.
E -100 to 1000 degrees C.

Temperature measurement resolution

+/- 0.2 degrees C.

Temperature measurement accuracy

+/- 0.2% of FS, or +/- 2 degrees C. typical

Cold junction compensation range

-20 to +85 degrees C.

Thermocouple connector

Type 1 standard mini connector for flat pin TC inputs

Data acquisition modes

Mode 1: autotrigger, logs TC data to memory on trigger event
Mode 2: log TC data on command from RF link
Mode 3: transmit TC data at progammable rate

Data acquisition software (DAS)

MicroStrain's Agile-Link™ ,Windows® XP, incl. w/ starter kits

Analog to digital (A/D) converter

Successive approximation type, 12 bits resolution

Data storage capacity

2 megabytes (~500,000 data points)

Linearized TC datalog or transmit rate

Programmable from 1 sample/minute to 100 samples/second

Data logging duration

Programmable from 100 to 65,535 samples, or log until memory capacity is full (at 1 sample/minute, 347 days maximum)

TC-Link™ node input power

Rechargeable 3.6 volt lithium ion, 200 milliamp-hour capacity standard; charger included with starter kits. TC-Link™ also supports an external battery pack or external DC power supply

TC-Link™ battery lifespan

~4 months with 1 Hz wireless RF update (70 microampere average current draw)
~7 months with 1 Hz data logging update (40 microampere average current draw)

Radio frequency (RF) transceiver carrier

2.4 GHz, direct sequence spread spectrum, license free worldwide

Range for RF transceiver link

70 meters (210 feet ) line of sight

RF data packet standard

IEEE 802.15.4, open communications architecture

USB programming & downloading

115,200 baud wireless

TC-Link™ sensor transceiver PCB size

60 by 35 by 15 mm (single channel standard)

TC-Link™ sensor transceiver standard enclosure

60 mm by 40 mm by 20 mm (single channel, with rechargeable lithium ion battery)

Base station enclosure size

100 mm by 30 mm by 25 mm (USB type)

Operating temperature

-20 to +85 degrees C.

 

 

Copyright © 2003 Endüstriyel & Bilimsel Test Teknolojileri Tasarımı ve Ar-Ge Mühendisliği